loading
Paidong Industrial Zone Qiligang,Yueqing City,Zhejiang province,China.
Paidong Industrial Zone Qiligang,Yueqing City,Zhejiang province,China.
Shopping Cart
  • No products in the cart.
  • MCB vs MCCB: A Practical Guide to Icu/Ics and IEC 60898 vs 60947-2

    This guide assumes you already know what a breaker is. If you need a primer on basic terms, read our intro pages first. Here we focus on ratings, standards, and real-world selection.

    TL;DR (Decision in 30 seconds)

    Use MCBs on final circuits with moderate prospective short-circuit current (PSC), typically under the IEC 60898-1 domain.

    Use MCCBs for distribution feeders or anywhere PSC is high and you need adjustable protection and higher Icu/Ics (IEC 60947-2).

    Select using: ① PSC at installation point (kA) → ② check Icu/Ics margin → ③ verify coordination/selectivity with upstream device → ④ confirm standard fit (60898 vs 60947-2).

    Where each device belongs (function & scope)

    MCB (Miniature Circuit Breaker)

    Optimized for final circuits (lighting, sockets, small loads). Fixed trip curves (B/C/D), compact footprint, typically lower breaking capacity, governed by IEC 60898-1.

    MCCB (Molded Case Circuit Breaker)

    Designed for distribution and higher-demand feeders. Higher short-circuit ratings, adjustable thermal/magnetic settings, accessories (aux contacts, shunt trips), governed by IEC 60947-2.

    Rule of thumb: If you are protecting a sub-main or anything with PSC near or above MCB’s rating, evaluate MCCB first.

    Short-circuit ratings demystified (what they truly limit)

     

    SymbolName (typical)What it means in practice
    IcuUltimate short-circuit breaking capacityThe maximum fault current the breaker can interrupt once and still provide minimal safety; it may not be fit for service afterwards.
    IcsService short-circuit breaking capacityThe proven breaking capacity at which the breaker can trip and remain serviceable. Often expressed as a % of Icu (e.g., 50%, 75%, 100%).
    IcmMaking capacityPeak current the device can make/close onto without damage (relevant for closing on fault).
    IcwShort-time withstandCurrent the device can carry for a defined short time (e.g., 1s) without tripping—important for selectivity.
    Inc / IcnConditional or rated breaking capacities in specific standardsYou’ll see Inc/Icn on some product lines; check the standard definition and test conditions. Do not treat them as identical to Icu/Ics.

    Selection tip: Always verify Ics at the actual PSC—a breaker with high Icu but a low Ics may trip once and need replacement.

    IEC 60898-1 vs IEC 60947-2 (which standard applies)

    IEC 60898-1: For household and similar installations (final circuits). Curves B/C/D, simplified rating presentation.

    IEC 60947-2: For industrial/commercial distribution. Detailed Icu/Ics/Icw specs, adjustable trips, coordination tables with upstream devices.

    Common mistake: Using 60898-style assumptions (e.g., B/C/D curves only) on a feeder that should be engineered under 60947-2 with proper short-time withstand and selectivity checks.

    How to size with PSC (a step-by-step method)

    Measure/estimate PSC (kA) at the breaker’s installation point (consider transformer size, impedance, cable length, and utility fault level).

    Choose the standard by circuit function: final circuit → 60898-1 (MCB); distribution/feeder → 60947-2 (MCCB).

    Check Icu and Ics ≥ PSC with margin (engineering practice often uses +20–25% headroom).

    Verify selectivity/coordination with upstream device using manufacturer tables (time-current curves & energy let-through).

    Apply the right trip curve or settings (B/C/D for MCB; adjustable thermal/magnetic for MCCB) based on inrush/start currents.

    Document: single-line diagram, ratings, and selectivity proof for inspection/maintenance.

    Quick selection matrix (printable aid)

     

    PSC at Point (kA)Circuit TypeTypical DeviceStandardNotes
    ≤ 6Final circuits (lighting, small outlets)MCB (B/C)60898-1Check curve vs inrush; verify downstream RCD selectivity if used.
    6–10Final circuits / small sub-boardsMCB (C/D) or small MCCB60898-1 / 60947-2Consider MCCB if PSC near limit or selectivity needed.
    10–25Sub-mains / distributionMCCB60947-2Adjustable trips, check Ics and Icw for selectivity.
    ≥ 25Main incomer / industrial feedersMCCB / ACB60947-2Engineer full selectivity and energy let-through.

    Common mistakes to avoid

    Confusing Icu with Ics (assuming service duty at Icu).

    Ignoring selectivity: a downstream trip should not black out the whole facility.

    Oversizing current rating to “solve nuisance trips” instead of using the correct curve/setting.

    Mixing standards without understanding the test assumptions behind each label.

    FAQ (for rich results)

    Q1. Is Ics always 100% of Icu?
    No. Many devices have Ics = 50–75% of Icu. Check the datasheet.

    Q2. Can I use an MCB on a feeder?
    Only if PSC and selectivity requirements are satisfied. In practice, MCCB is preferred for feeders.

    Q3. Do B/C/D curves exist on MCCB?
    MCCBs typically use adjustable thermal/magnetic settings rather than fixed B/C/D curves.

    Q4. What about UL ratings?
    UL standards use different terms and tests (e.g., SCCR, interrupting rating). Don’t mix with IEC figures.

    Johnson Lim

    Johnson Lim

    Johnson Lim is the General Manager of Changyou Technology and has over 10 years of experience in circuit protection technology and residential electrical safety. He is committed to developing and producing safer and smarter electrical products.

      Table of Contents